The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between CC-Link and Interbus Fiber Optic networks.
FAST COPYING OF I/O DATA
The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as a Slave on both networks. The data transmission is completely transparent with a maximum data capacity of 512 bytes in each direction.
EASY CONFIGURATION - NO PROGRAMMING REQUIRED!
The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.
CC-Link Slave interface
CC-Link Slave settings can be made either via on-board switches, or by importing the provided .CSP file into engineering tool of the controlling PLC.
- Complete CC-Link slave Version 1 and 2 functionality
- CC-Link Conformance BTP-05027-B specification
- Transparent CC-Link communication (Standard Mode)
- PLC Profile compliant communication (PLC profile mode)
- Max. 896 bits/128 words (368 bytes) of I/O data in each direction
- Supports CC-Link baudrates 156 kbit/s – 10 Mbit/s
- Up to 4 occupied stations
- Up to 8 extension cycles (version 2 only)
- CC-Link configuration via on-board switches or via .CSP file
- 1x 5-pin, 5.08 Phoenix plug network connector
Interbus Fiber Optic Slave Interface
Interbus Slave address settings can are automatically detected by the controlling PLC.
- Complete Interbus functionality according to EN 50170
- Fiber Optic features FSMA standard connectors conforming to IEC874-2 and DIN47258
- Based on OPC chipset with support for optical diagnostics
- Transmission Media: Plastic fibre, core 180um, clad 1000um: HCS (glass) fibre, core 200um, clad 230 um
- Max. 20 bytes of process data (512 bytes with PCP) in each direction
- PCP V.2.0. (0, 1, 2, or 4 words)
- Interbus baudrate 500 kbit/s – 2 Mbit/s
- Automatic slave address detection by controlling PLC master
- 1x HFBR-2505C and 1x HFBR-1505C Fiber Optic network connectors
Order Code | AB7892 |
Price group | C |
Included components | Resource CD, USB configuration cable, Quick start guide, manuals. Anybus Configuration Manager software. For bulk pack orders, all configuration software can be downloaded under "files and documentation" from this website. (Power supply not included) |
Optional Accessories | *Extra wide DIN-clip for flat mounting (Order Code SP1784) |
Guarantee | 3 years |
Especificaciones Tecnicas
Dimensions (L•W•H) | 114 x 44 x 127mm or 4,49 x 1,73 x 5,00" |
Weight | 400g or 0,880 lbs |
Operating temperature | -25 to +65 °C or -13 to +149 °F |
Storage temperature | -40 to +85 °C or -40 to +185 °F |
Power supply | 24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector |
Current consumption | max. 400mA (Typical 200mA) |
Enclosure material | Aluminium and plastic |
Installation position | Vertical / Flat* |
Galvanic isolation | YES, on both BUS/Ethernet side |
Mechanical rating | IP20, NEMA rating 1 |
Mounting | DIN-rail (EN 50022 standard) |
I/O configuration | via USB port with Anybus Configuration Manager software |
Certifications | CE, CULUS, ATEX/Haz.Loc |
Referencia | Descripcion |
---|---|
AB7892 | Anybus X-gateway – CC-Link Slave - Interbus FO Slave |
Documentacion | Anybus X-gateway Datasheet |
Documentacion | CC-Link Slave Conformance Certificate |
Documentacion | Datasheet |
Documentacion | Firmware Download Anybus X-gateway Classic |
Documentacion | Installation Guide - CC-Link Slave |
Documentacion | Installation Guide Anybus X-gateway |
Documentacion | Installation Guide |
Documentacion | Network Guide - CC-Link Slave |
Documentacion | Network Guide - Interbus Fibre Optic Slave |
Documentacion | User Manual Anybus X-gateway |
Descargas | CSP Files For CC-Link Slave |
Descargas | Drawings of X-gateway |
Descargas | EU Declaration Of Conformity, ATEX Conformance Certificate |
Descargas | Firmware Download Tp |
Descargas | How To Configure Anybus Interbus slave Module With IBS CMD G4 For Interbus |
Descargas | How To Configure Anybus Module With CC-Link And Mitsubishi PLC |