Anybus X-gateway – CC-Link IE Field Slave - PROFIBUS Slave
Características destacadas
- undefined
Descripción
The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between CC-Link IE Field and PROFIBUS networks.
FAST COPYING OF I/O DATA
The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as a Slave on both networks. The data transmission is completely transparent with a maximum data capacity of 512 bytes in each direction.
EASY CONFIGURATION - NO PROGRAMMING REQUIRED!
The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.
CC-Link IE Field interface
CC-Link IE Field Slave settings can be made either via on-board switches, or by importing the provided .CSP file into engineering tool of the controlling PLC.
- CC-Link IE Field interface of the X-gateway is conformance tested and approved by CLPA
- CC-Link Specification (Profile), publication BTP-05028-B
- Acts as a CC-Link IE Field Network Intelligent Device Station
- Max 512 bytes Input and 512 bytes I/O data
- On CC-Link IE Field: Max of 832 I/O points and 204 words Input and 832 I/O points and 204 words Output
- Baudrate 1 Gbit/s fixed operation
- TCP/IP settings configurable with web-page, Configuration Tool, DHCP or ARP
- CC-Link IE Field station setting via on-board switches
- 2x RJ-45 ports available simultaneously
PROFINET I/O Device/Slave interface
PROFINET IO Device/Slave settings can be made either via the built-in web interface, or by importing the provided .GSDML file into engineering tool of the controlling PLC.
- Complete PROFINET-IO Soft-Real-Time (RT) communication
- Max 512 bytes of Input and 512 bytes of Output data
- Up to 64 slots / 1 sub slot
- Cyclic data exchange (10 ms cycle time)
- Acyclic Data exchange (Record Data Requests)
- Baud rate 100 Mbit/s
- Integrated FTP server provides easy file management using standard FTP clients
- Web server with dynamic data capability and Server Side Include (SSI) capability
- Email client with dynamic data capability and Event-triggered email handling
- TCP/IP Configuration via DCP (Discovery and Configuration Protocol)
- PROFINET uplink configuration via web interface or .GSDML file
- Integrated switch allowing for a daisy-chain topology
- Dual RJ-45 network ports available simultaneously
Order Code | AB7959 |
Price group | A |
Included components | Resource CD, USB configuration cable, Quick start guide, manuals. Anybus Configuration Manager software. Anybus OPC server software. (single-piece only) For bulk pack orders,all configuration software can be downloaded under "files and documentation" from this website. (Power supply not included) |
Optional Accessories | *Extra wide DIN-clip for flat mounting (Order Code SP1784) Anybus IPconfig Tool - Utility for module TCP/IP configuration (Windows 32/64-bit) Downloadable under "Files and Documentation" |
Guarantee | 3 years |
Especificaciones Tecnicas
Dimensions (L•W•H) | 114 x 44 x 127mm or 4,49 x 1,73 x 5,00" |
Weight | 400g or 0,880 lbs |
Operating temperature | -25 to +65 °C or -13 to +149 °F |
Storage temperature | -40 to +85 °C or -40 to +185 °F |
Power supply | 24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector |
Current consumption | max. 400mA (Typical 200mA) |
Enclosure material | Aluminium and plastic |
Installation position | Vertical / Flat* |
Galvanic isolation | YES, on both BUS/Ethernet side |
Mechanical rating | IP20, NEMA rating 1 |
Mounting | DIN-rail (EN 50022 standard) |
I/O configuration | via USB port with Anybus Configuration Manager software |
Certifications | CE, CULUS, ATEX/Haz.Loc |
Referencia | Descripcion |
---|---|
AB7959 | Anybus X-gateway – CC-Link IE Field Slave - PROFIBUS Slave |
Documentacion | Anybus X-gateway Datasheet |
Documentacion | CC-Link Slave Conformance Certificate |
Documentacion | Conformance Certificate Profibus Slave |
Documentacion | Datasheet |
Documentacion | Firmware Download Anybus X-gateway Classic |
Documentacion | Installation Guide - PROFIBUS Slave Interface |
Documentacion | Installation Guide Anybus X-gateway |
Documentacion | Network Guide - CC-Link IE Field |
Documentacion | Network Guide - PROFIBUS Slave |
Documentacion | User Manual ABX |
Descargas | Anybus Configuration Manager X-gateway (for Win 7, Win 8, Win XP and Win 2000) |
Descargas | Drawings of X-gateway |
Descargas | EU Declaration Of Conformity, ATEX Conformance Certificate |
Descargas | Firmware Download Tp |
Descargas | GSD File For Profibus DP-DPV1 |
Descargas | How To Configure Anybus Profibus Slave Module With Siemens Step 7 |
Descargas | IPConfig - Utility for module TCP-IP configuration |