Anybus X-gateway – CANopen Master – Modbus RTU Slave

Características destacadas

  • Fast copying of cyclic I/O data between a CANopen and Modbus RTU network (5 ms)
  • Fulll CANopen Master/Manager functionality, eliminates the need for an PLC controller on the CANopen network
  • Connects up to 126 CANopen slave devices
  • Proven and tested with all PLC manufacturers
  • Easy CANopen configuration via the included Anybus Configuration Manager software. No programming required
  • Robust stand-alone housing for use in harsh industrial environments
  • Global free technical support and consultancy

Descripción

The Anybus X-gateway CANopen provides a seamless connection between a Modbus RTU network and a secondary CANopen sub-network. This makes it possible to integrate CANopen devices into a Modbus RTU PLC system.

FAST COPYING OF I/O DATA
The X-gateway's primary function is fast transfer of cyclic I/O data between the two networks. I/O data from the Modbus RTU network is written into CANopen objects that can be mapped into CANopen PDOs and vice versa. The gateway acts as a full Master/Manager on the CANopen network and as a Slave on the Modbus RTU network. The data transmission between the two networks is completely transparent with a maximum data capacity of 510 bytes in each direction.

EASY CONFIGURATION - NO PROGRAMMING REQUIRED!
CANopen configuration can easily be made through the included Anybus Configuration Manager CANopen software, or with any other standard CANopen configuration tool. No programming skills are needed. 

CANopen Master/Manager Interface

  • CANopen Master/Manager implementation according to the CANopen specification DS301 v4.0.2.
  • Connects up to 126 CANopen slaves
  • Network Management (NMT) messages, to configure and initialize the network.
  • Supporting 128 Receive PDOs and 128 Transmit PDOs, each can transfer up to 8 bytes.
  • Up to 510 bytes of cyclic data in each direction (PDO)
  • PDO message types: COS (Change of State), Cyclic Synchronous, Acyclic Synchronous.
  • Synchronization Object (SYNC) is used for synchronizing PDO communication.
  • Heartbeat Mechanism to monitor the status of nodes.
  • Node Guarding/Life Guarding Protocol provides possibility to guard slaves or the master.
  • EMCY (Emergency Object) is used for error reporting.
  • LSS master functionality
  • Can also function as a CANopen Slave

Modbus RTU Slave interface 

Modbus RTU network address settings made via on-board configuration switches 

  • Complete Modbus RTU slave functionality
  • Max 512 bytes of Input and 512 bytes of Output data
  • Modbus diagnostics support
  • Configuration via on-board DIP switches
  • Modbus RTU baudrate 12-57,6 kbit/s
  • 1x D-sub 9-pin female network connector
Order Code AB7305
Included components     Resource CD, Quick start guide, manuals. Anybus Configuration Manager CANopen software. For bulk pack orders, all configuration software can be downloaded under "files and documentation" from this website. (Power supply not included)
Optional Accessories USB-CAN configuration adapter (Order Code 012670)  
Guarantee3 years 

Especificaciones Tecnicas

Dimensions (L•W•H) 120 x 75 x 27mm or 4,72 x 2,95 x 1,06"
Weight150g or 0,33 lbs
Operating temperature-25 to +55 °C or 0 to +131 °F
Storage temperature -40 to +85 °C or -40 to +185 °F
Power supply24 VDC
Current consumption Typical 150mA
Configuration portUSB (USB to CAN cable not included)
Configuration Switches On-board for CANopen node address and baud rate setting
CANopen connectorD-sub 9 Male (Included)
Fieldbus/Ethernet connector(See interface details above)
Galvanic isolation On both CAN and BUS/Ethernet side
Mechanical ratingIP20, NEMA rating 1
MountingDIN-rail (EN 50022 standard)
CANopen baudrate20 kbit/s - 1 Mbit/s
CertificationsCE, CULUS, ATEX/Haz.Loc