Anybus X-gateway – EtherCAT Slave - Interbus FO Slave
Características destacadas
- Fast copying of cyclic I/O data between two networks (10-15 ms)
- Proven and tested with all PLC manufacturers
- Supports up to a maximum of 512 bytes of Input and Output data in each direction
- Optional control and status information added to the I/O data for diagnostic purposes
- Robust stand-alone housing for use in harsh industrial environments
- Global free technical support and consultancy
Descripción
The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between EtherCAT and Interbus Fiber Optic networks.
FAST COPYING OF I/O DATA
The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as a Slave on both networks. The data transmission is completely transparent with a maximum data capacity of 512 bytes in each direction.
EASY CONFIGURATION - NO PROGRAMMING REQUIRED!
The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.
EtherCAT Slave interface
EtherCAT Slave settings can be made by importing the provided .XML file into engineering tool of the controlling PLC.
- Complete EtherCAT slave according to DS 301 V4.022
- Supports CANopen over EtherCAT
- Max 512 bytes of Input and 512 bytes of Output data (PDO + SDO)
- Baudrate 100 Mbit/s full duplex
- 4 FMMU channels (can be used freely by the EtherCAT master for any purpose.)
- 4 SM channels
- Bit-oriented FMMU operation
- Position addressing, node addressing and logical addressing
- PDI Watchdog
- Output I/O Sync Manager Watchdog
- Integrated switch allowing for a daisy-chain topology
- 2x RJ45 EtherCAT connectors
Interbus Fiber Optic Slave Interface
Interbus Slave address settings can are automatically detected by the controlling PLC.
- Complete Interbus functionality according to EN 50170
- Fiber Optic features FSMA standard connectors conforming to IEC874-2 and DIN47258
- Based on OPC chipset with support for optical diagnostics
- Transmission Media: Plastic fibre, core 180um, clad 1000um: HCS (glass) fibre, core 200um, clad 230 um
- Max. 20 bytes of process data (512 bytes with PCP) in each direction
- PCP V.2.0. (0, 1, 2, or 4 words)
- Interbus baudrate 500 kbit/s – 2 Mbit/s
- Automatic slave address detection by controlling PLC master
- 1x HFBR-2505C and 1x HFBR-1505C Fiber Optic network connectors
Order Code | AB7690 |
Price group | C |
Included components | Resource CD, USB configuration cable, Quick start guide, manuals. Anybus Configuration Manager software. For bulk pack orders,all configuration software can be downloaded under "files and documentation" from this website. (Power supply not included) |
Optional Accessories | *Extra wide DIN-clip for flat mounting (Order Code SP1784) Anybus IPconfig Tool - Utility for module TCP/IP configuration (Windows 32/64-bit) Downloadable under "Files and Documentation" |
Guarantee | 3 years |
Especificaciones Tecnicas
Dimensions (L•W•H) | 114 x 44 x 127mm or 4,49 x 1,73 x 5,00" |
Weight | 400g or 0,880 lbs |
Operating temperature | -25 to +65 °C or -13 to +149 °F |
Storage temperature | -40 to +85 °C or -40 to +185 °F |
Power supply | 24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector |
Current consumption | max. 400mA (Typical 200mA) |
Enclosure material | Aluminium and plastic |
Installation position | Vertical / Flat* |
Galvanic isolation | YES, on both BUS/Ethernet side |
Mechanical rating | IP20, NEMA rating 1 |
Mounting | DIN-rail (EN 50022 standard) |
I/O configuration | via USB port with Anybus Configuration Manager software |
Certifications | CE, CULUS, ATEX/Haz.Loc |
Referencia | Descripcion |
---|---|
AB7690 | Anybus X-gateway – EtherCAT Slave - Interbus FO Slave |
Documentacion | Anybus X-gateway Datasheet |
Documentacion | Datasheet |
Documentacion | EtherCAT Conformance Certificate |
Documentacion | Firmware Download Anybus X-gateway Classic |
Documentacion | Installation Guide - EtherCAT Slave |
Documentacion | Installation Guide Anybus X-gateway |
Documentacion | Installation Guide |
Documentacion | Network Guide - EtherCAT Slave |
Documentacion | Network Guide - Interbus Fibre Optic Slave |
Documentacion | User Manual ABX |
Descargas | Anybus Configuration Manager X-gateway (for Win 7, Win 8, Win XP and Win 2000) |
Descargas | Firmware Download Tp |
Descargas | How To Configure Anybus EtherCAT Slave Module With Beckhoff PLC |
Descargas | How To Configure Anybus Interbus slave Module With IBS CMD G4 For Interbus |
Descargas | Omron NJ Controller EtherCAT Master Connected With Anybus X-gateway |
Descargas | XML Files For EtherCAT |