Interface | |
Ethernet interface | Auto-detecting 10BaseT/100BaseTx/1000BaseT (GigaLAN) Connector 8P8C (RJ45) |
Wireless interface | Optional, uses IEEE 802.11b/g/n as Access Point or Client Embedded module or USB expansion available |
Protocols | TCP/IP, DHCP, ICMP, HTTP, DNS, UDP, UPnP/SSDP, Modbus/TCP, Modbus/RTU, Modbus/ASCII |
Serial interface | RS232/422/485 selected by software |
No. of port | 1x DSUB 9 male connector (as PC) |
Available Modes | RS232 full duplexRS422 full duplexRS485 4 wire, full duplexRS485 2 wire, half duplex |
Signals | RS232: TxD,RxD, RTS,CTS, DTR,DSR, DCD, RI, GNDRS422: Tx+/-, Rx+/-, GNDRS485 2 wire: Data+/-, GNDRS485 4 wire: Tx+/-, Rx+/-, GND |
RS485 Data control | Controlled by ART (Automatic Receive Transmit control) |
Expansion port | USB 2.0 High Speed, for WLAN |
Serial Performance | |
Speed | up to 115.2 kbps for Modbus RS232: up to 1000 kbps, RS422/485: up to 3.7Mbps |
Parity | None, even, odd, mark, space |
Data bits | 7, 8 |
Stop bits | 1, 2 |
Operating Modes | |
Modbus RTU/ASCII | Modbus RTU or Modbus ASCII protocol selected for each serial port individually |
DirectMappingMode | Direct mapping of Modbus addresses to serial ports or TCP connections |
PromiscousMode | Mapping of serial ports to TCP connections |
Power and Environment | |
Connector | 3-pin Terminal Block with Protective Earth |
Power requirements | 9 - 54V DC, 0.3A @ 12V, 4W |
Dimension | 115×73×25 mm³ (W×L×H) |
Operating Temp | −20°C - 65°C |
Storage Temp | −20°C – 85°C |
Case | SECC sheet metal (1mm) |
Weight | 0.25kg |
Mounting | DIN RailWall mount |
Special Features | |
Installation | DIP switches set a defined temporary IP Address to contact via WEB Browser |
Operating mode | Promiscous ModeMessages received from the network are sent to the serial port, messages from the serial port are sent to the connected network host.Mapped ModeReceived messages are scanned for their target address. This address is found in a table, the message is sent to the defined connection (serial or TCP). |
Modbus Master Multiplexing | An extension to the standard. Slaves on serial lines may answer requests from multiple masters. The masters connect to ModGate+ by Modbus/TCP. |
Configuration | Configuration over WEB Browser |
Detection | Announces presence in the network via Universal Plug and Play (UPNP) protocol |
DNS | Domain Name Server support |
Serial Interface | Serial Interface configurable by software This also enables internal Termination for RS485 |
Firmware | Firmware update over WEB Browser |
LEDs | LEDs for Power, Ready, WLAN, serial Tx, Rx, Ethernet Link, Speed |
Security | |
Password access | Webinterface is password protected. The password can be changed in the Webinterface. |