Anybus BACnet to Modbus Gateway
Características destacadas
- Enables central control and supervision of Modbus devices within Building Automation and HVAC applications
- Handles conversion between Modbus (RTU, ASCII, TCP) and BACnet/IP
- Additional routing function between Modbus RTU and TCP
- Connects up to 30 Modbus RTU/ASCII/TCP server/slave devices to BACnet/IP (processing up to 1000 Modbus registers).
- Each connected Modbus device appears as an individual BACnet compliant device
- Excel tool and instructions for creating Modbus Device Profiles are available
- A resident web server allows for commissioning, and troubleshooting via a standard web browser
- External terminating resistors are included in the package. (No termination by default in the product.)
- Robust stand-alone metal housing for use in harsh industrial environments
- Global free technical support and consultancy
Descripción
The Anybus BACnet to Modbus gateway allows Modbus devices to communicate on a BACnet/IP network. The gateway works as a translator between the two networks allowing Modbus RTU, ASCII or TCP devices to show up as individual BACnet-compliant devices on a BACnet/IP network.
Modbus Master/Client
The gateway functions as a Serial Modbus RTU/ASCII Master to Modbus devices connected via RS232/485 serial port of the gateway and as a Modbus TCP Client to the connected Modbus TCP servers. On the other side, the gateway provides Slave functionality to the BACnet/IP devices connected to the Ethernet port. A mix of both Modbus Serial and Modbus TCP devices can be connected at the same time.
Designed for use within Building and HVAC applications
With its rugged industrial design, it enables central control and supervision of Modbus devices for example in Building Automation and HVAC industry (Heating Ventilation and Air-Conditioning) applications, such as, Boiler controls, Variable speed drives and with Metering applications.
Easy web-based Device Profile Creation
You will need to create a device profile for each Modbus device and upload this to the gateway. HMS offers a library of common device profiles. If one is not available for your device, HMS provides a tool and instructions on how to create a device profile for your Modbus device. You can then do commissioning and troubleshooting in the included web interface.
BACNet/IP Server features
- Conforms to ASHRAE 135-2004, Annex J, B-ASC Profile
- 100/100 Mbit/s
Modbus TCP Client features
- Conforms to Modbus Appl. Protocol Spec. V1.1b,
- Support for Modbus Messaging on TCP/IP Impl. Guide V1.0b
- Modbus TCP Client functionality connecting up to 30 Modbus servers
- 10/100 Mbit/s
- Routing function between TCP and RTU
Serial Modbus features
- Modbus over Serial Line Spec. and Implementation Guide V1.02b
- RS-485 only
- Modbus RTU Master and Modbus ASCII Master connecting up to 30 Modbus serial slave devices
- Baudrate 2.4, 4.8 9.6, 19.2, 38.4, 57.6, 76.8, 115.2 kbps
- Routing function between RTU and TCP
Order Code | 024090 |
Stock Item | YES |
Included components | Gateway leaflet, installation sheet and external discrete terminating resistor. (Power supply not included) |
Guarantee | 3 years |
Especificaciones Tecnicas
Dimensions (L•W•H) | 131 x 41 x 96 mm or 5,15 x 1,61 x 3.79 inches | |
Weight | 100g or 0,35 lbs | |
Operating temperature | 0 to +60 °C or 32 to +140 °F | |
Storage temperature | -40 to +85 °C or -40 to +185 °F | |
Power supply | 24 VAC ± 10%, 10 VA 47-63 Hz 24 VDC ± 10% 6 W | |
Bias and termination | Internal jumpers allow flexible bias and termination options. They can be removed for mid-span installations. | |
LED indicators | Serial: TX, RX Activity | |
LED indicators | Ethernet: Link (10 or 100 Mbit, Activity) Duplex (Half, full, collision) | |
Ethernet connector | 1x shielded RJ45 | |
Serial port | Removable 5-pin terminal supporting RS-485 | |
Galvanic isolation | On both serial Modbus and Ethernet side | |
Mechanical rating | IP30, Metal housing | |
Mounting | DIN-rail (EN 50022 standard) | |
Certifications | CE, CULUS, ATEX/Haz.Loc |
Referencia | Descripcion |
---|---|
024090 | Anybus BACnet to Modbus Gateway |
Documentacion | Anybus BACnet To Modbus Gateway Using The Anybus Profile Builder |
Documentacion | Anybus BACnet to Modbus gateway |
Documentacion | BACnet Units Supported by Anybus BACnet to Modbus gateway |
Documentacion | Conformance Certificate |
Documentacion | Datasheet |
Documentacion | EU Declaration of Conformity Anybus BACnet to Modbus Gateway |
Documentacion | Installation Guide |
Documentacion | Mapping Modbus Registers to BACnet® Objects |
Documentacion | Quick guide - Getting started Anybus BACnet Gateway |
Documentacion | User Manual |
Descargas | Anybus BACnet Device Profile Verification |
Descargas | Anybus Profile Builder |
Descargas | Firmware BACnet Gateway |
Descargas | How to configure the BACnet to Modbus gateway (video) |