Anybus X-gateway – PROFIBUS Slave - CANopen Slave

Características destacadas

  • Fast copying of cyclic I/O data between PROFIBUS and CANopen (10-15 ms)
  • Proven and tested with all PLC manufacturers
  • Supports up to a maximum of 512 bytes of Input and Output data in each direction
  • Optional control and status information added to the I/O data for diagnostic purposes
  • Robust stand-alone housing for use in harsh industrial environments
  • Global free technical support and consultancy

Descripción

The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between PROFIBUS and CANopen networks.

FAST COPYING OF I/O DATA

The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as an Slave on the PROFIBUS network and as a Slave on the CANopen network. The data transmission between the two networks is completely transparent with a maximum data capacity of 512 bytes in each direction.

EASY CONFIGURATION - NO PROGRAMMING REQUIRED!

The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.

PROFIBUS Slave interface

PROFIBUS Slave settings can be made either via on-board switches, or by importing the provided .GSD file into engineering tool of the controlling PLC. 

  • Complete PROFIBUS-DP/DPV1 Slave functionality according to extensions of EN 50170
  • Supports Class 1 & Class 2 services
  • Automatic baudrate detection up to 12Mbit/s
  • Supports PA baud rate 45.45 kbit/s
  • Max. Cyclic I/O data 244 bytes Input and 244 bytes Output, max 328 bytes total (in+out)
  • Acyclic User Parameter data / Diagnostics length - up to 237 bytes
  • Supports PROFIBUS features: Sync and Freeze and Watchdog
  • PROFIBUS slave settings via on-board switches or vis .GSD file
  • 1x D-sub 9-pin female PROFIBUS connector

CANopen Slave interface

CANopen Slave settings can be made either via on-board switches, or by importing the provided .EDS file into engineering tool of the controlling PLC.

  • Complete CANopen slave functionality according to CANopen Version 4.02
  • Max 512 bytes of Input and 512 bytes of Output data (PDO + SDO)
  • Customizable PDO mapping
  • Up to 80 RPDO’s and 80 TPDO’s
  • Transmission types: PDO Sync, Change-of-state, Event based and RTR
  • Network store/restore functionality
  • Heartbeat & Node Guarding support
  • Supports CANopen baudrates 10 kbit/s – 1 Mbit/s
  • CANopen configuration via .EDS file or via on-board rotary switches
  • 1x D-sub 9-pin male CANopen connector
Order Code AB7849
Stock ItemYES
Included components     Resource CD, USB configuration cable, Quick start guide, manuals. Anybus Configuration Manager software. For bulk pack orders, all configuration software can be downloaded under "files and documentation" from this website. (Power supply not included)
Optional Accessories *Extra wide DIN-clip for flat mounting (Order Code SP1784)   
Guarantee3 years 

Especificaciones Tecnicas

Dimensions (L•W•H) 114 x 44 x 127mm or 4,49 x 1,73 x 5,00"
Weight400g or 0,880 lbs
Operating temperature-25 to +65 °C or -13 to +149 °F
Storage temperature-40 to +85 °C or -40 to +185 °F
Power supply24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector
Current consumption max. 400mA (Typical 200mA)
Enclosure material Aluminium and plastic
Installation positionVertical / Flat*
Galvanic isolationYES, on both BUS/Ethernet side
Mechanical ratingIP20, NEMA rating 1
MountingDIN-rail (EN 50022 standard)
I/O configurationvia USB port with Anybus Configuration Manager software
CertificationsCE, CULUS, ATEX/Haz.Loc

Referencia Descripcion
AB7849 Anybus X-gateway – PROFIBUS Slave - CANopen Slave