EtherNet/IP to Modbus-TCP Linking Device

EtherNet/IP to Modbus-TCP Linking Device

Minimize costs when connecting Modbus-TCP networks/devices to ControlLogix® or CompactLogix® controllers with an EtherNet/IP interface.
Protocolos: Ethernet/IP Modbus TCP

Características destacadas

  • Minimize costs when connecting Modbus-TCP devices to your PLC. More cost-efficient than an in-chassis solution
  • Allows support for "Big Data" - handling up to 8 KB of I/O data over multiple I/O connections on EtherNet/IP
  • Speed up configuration through a seamless integration with Studio 5000 Logix Designer
  • Compatible with all ControlLogix and CompactLogix PLC’s supporting EtherNet/IP
  • Easy to setup with Custom Add-On Profile with no programming required!
  • Everything configured through Studio 5000, no 3rd party software or licenses needed
  • Dynamically generates data structures in Studio 5000 with no required user logic
  • Supports automatic generation of named and structured Studio 5000 controller tags
  • Configuration backup in Studio 5000 project and Controller memory

Descripción

EtherNet/IP to Modbus-TCP Linking Device

Minimize costs when connecting Modbus-TCP networks/devices to ControlLogix® or CompactLogix® controllers with an EtherNet/IP interface.


Fast Copying I/O Data (Big Data Support)

The Linking Device primary function is with the fast transfer of large I/O data between the two networks. This offloads your Logix PLC from working with additional calculations. The Linking Device acts as a slave (adapter) on EtherNet/IP and as a powerful client (master), on the Modbus-TCP network, handling up to 8 KB of I/O data. The data transmission between the two networks is completely transparent.


Seamless integration with Studio 5000

With its unique Studio 5000® Logix designer integration, everything is accessible from within Studio 5000, including Modbus-TCP network configuration. No extra 3rd-party software or licenses needed.


Connect, configure, done

EtherNet/IP Linking Devices are configured using a Custom Add-On Profile for Studio 5000 Logix Designer which dynamically generates data structures based on the configuration. No ladder logic files (add on instructions) needed.

Furthermore, it also supports automatic generation of named and structured Studio 5000 controller tags, which eliminates the need to create alias tags.

Modbus-TCP Client/Master interface

The Linking Device has an integrated powerful Modbus-TCP Client/Master interface

modbus-tcp client FEATURES

  • Up to 4 KB of cyclic and acyclic I/O data in each direction
  • Controls up to 64 Modbus-TCP server (slaves) connections and transactions
  • Downlink Live List providing Modbus-TCP transaction status to uplink PLC
  • Control and Status words for downlink network control/status
  • Supports the generation of Process Variable Data Tags on Modbus command level
  • Supported Modbus-TCP functions: 1, 2, 3, 4, 5, 6, 15, 16, 23
  • Dual RJ-45 ports available simultaneously. 10/100Mbit operation in full or half-duplex
  • Modbus-TCP network configuration accessed through Studio 5000

EtherNet/IP Adapter interface

The Linking Device has the very latest ODVA EtherNetIP adapter functionality

ETHERNET/IP ADAPTER FEATURES 

  • Dual EtherNet/IP ports 10/100Mbit, full or half-duplex operation
  • Beacon-based DLR (Device Level Ring) and linear network topology supported
  • Support for multiple (Exclusive Owners) I/O connections (Max 10)
  • ODVA EtherNet/IP conformance tested 

Technical specifications

Dimensions  (L•W•H)  110 x 35 x 101mm or 4,33 x 1,38 x 3,98"
Weight  160 g, 0,35 lb
Operating temperature -25 to +70 °C  or  -13 to +158 °F 
Storage temperature
-40 to +85 °C  or  -40 to +185 °F 
Power supply  24 VDC +/- 20%
Current consumption
Typical 150 mA @ 24 V
Enclosure material PC ABS, UL94 VO
Installation position   Vertical
Galvanic isolation        
YES, on both BUS/Ethernet side   
Mechanical rating  IP20, NEMA rating 1
Mounting DIN-rail (EN 50022 standard) or Wall mount
Modbus-TCP baudrate 10/100 Mbit/s autodetect
Modbus-TCP connector 2x RJ45
Modbus-TCP address  Any valid IP address can be used 
EtherNet/IP baudrate  10/100 Mbit/s autodetect 
EtherNet/IP connector  2x RJ45
EtherNet/IP address  Any valid IP address can be used 
TCP/IP settings  Configurable via BOOTP-DHCP server or via Anybus IP config  
SD Memory Card slot  YES, enabling easy module replacement 
Certifications
ODVA, CE, CULUS  (ATEX/Haz.Loc - PENDING)

Ordering information

Order Code  HMS-EN2MB-R 
Included components  HMS-EN2MBR Linking Device, Installation guide, (Power supply not included)
Guarantee  3 years 

Referencia Descripcion
HMS-EN2MB-R Minimize costs when connecting Modbus-TCP networks/devices to ControlLogix® or CompactLogix® controllers with an EtherNet/IP interface.
Documentacion Installation Sheet
Documentacion User Manual
Documentacion Datasheet
Si continuas utilizando este sitio aceptas el uso de cookies. más información